SG05LP1 AM2-P Single-Phase Hybrid · 3.6–10 kW
SUN-3.6/5/6/7/7.6/8/10K-SG05LP1-AU-AM2-P
3.6–10 kW
48 V low-voltage single-phase hybrid in seven sizes from 3.6 to 10 kW, all the same size and 24.9 kg weight. Dual MPPT, up to 210 A battery charge/discharge, AC-coupling to retrofit existing PV, up to 16 units in parallel and six time periods for battery charging/discharging.
- Available ratings
- 3.6 / 5 / 6 / 7 / 7.6 / 8 / 10 kW — SUN-3.6K to SUN-10K-SG05LP1-AU-AM2-P
- Rated AC power
- 3600–9999 W (the 10K is rated 9999 W)
- Phase
- Single (230 / 240 V)
- Battery
- 48 V (40–60 V), 90–210 A
- Max. PV input
- 5760–16000 W
- MPP trackers
- 2 (1+1 strings on 3.6–6 kW · 2+2 on 7–10 kW)
- Max. efficiency
- 97.6%
- Parallel
- Up to 16 units
- Warranty
- 10 years
Specifications
Battery input
- Battery type
- Lead-acid or Lithium-ion
- Battery voltage range
- 40–60 V (48 V rated)
- Max. charging / discharging current
- 90 / 120 / 135 / 175 / 190 / 190 / 210 A (3.6 / 5 / 6 / 7 / 7.6 / 8 / 10 kW)
- Charging strategy (Li-ion)
- Self-adaption to BMS
- Number of battery inputs
- 1
PV input
- Max. PV access power
- 7200–20000 W (per size: see model table)
- Max. PV input power
- 5760–16000 W (per size: see model table)
- Max. PV input voltage
- 500 V
- Start-up voltage
- 125 V
- MPPT voltage range
- 150–425 V
- Full-load MPPT voltage range (manual)
- 300–425 V (3.6–6 kW) · 200–425 V (7–8 kW) · 250–425 V (10 kW)
- Rated PV input voltage
- 370 V
- Max. operating PV input current
- 18+18 A (3.6–6 kW) · 32+32 A (7–10 kW)
- Max. input short-circuit current
- 27+27 A (3.6–6 kW) · 48+48 A (7–10 kW)
- No. of MPP trackers / strings
- 2 / 1+1 (3.6–6 kW) · 2 / 2+2 (7–10 kW)
AC output
- Rated AC input/output active power
- 3600 / 5000 / 6000 / 7000 / 7600 / 8000 / 9999 W
- Rated / max. AC input/output apparent power
- 3600 / 5000 / 6000 / 7000 / 7600 / 8000 / 9999 VA
- Rated (= max.) AC input/output current
- 15.7 / 21.8 / 26.1 / 30.5 / 33.1 / 34.8 / 43.5 A
- Max. continuous AC passthrough (grid→load)
- 35 A (3.6–5 kW) · 40 A (6 kW) · 50 A (7–10 kW)
- Peak power (off-grid)
- 2× rated power, 10 s
- Power factor adjustment range
- 0.8 leading to 0.8 lagging
- Rated voltage / range
- 230 / 240 V, 0.85Un–1.1Un
- Grid frequency / range
- 50 Hz / 45–55 Hz
- Grid connection form
- L+N+PE
- Total current harmonic distortion (THDi)
- <3% (of nominal power)
- DC current injection
- <0.5% In
Generator & backup
- Generator nominal input voltage
- 230 / 240 V, 50 Hz
- Generator rated input current
- 15.7 / 21.8 / 26.1 / 30.5 / 33.1 / 34.8 / 43.5 A
- Backup nominal output voltage
- 230 / 240 V, 50 Hz
- Backup rated output current
- 15.7 / 21.8 / 26.1 / 30.5 / 33.1 / 34.8 / 43.5 A
- Backup rated apparent power
- 3600 / 5000 / 6000 / 7000 / 7600 / 8000 / 9999 VA
Efficiency
- Max. efficiency
- 97.6%
- Euro efficiency
- 96.5%
- MPPT efficiency
- >99%
Protection
- Integrated protection
- DC reverse polarity, AC output overcurrent / overvoltage / short circuit, thermal, DC component monitoring, anti-islanding (active frequency shift), DC switch, insulation impedance detection, residual current detection; AFCI optional
- Surge protection level
- TYPE II (DC), TYPE II (AC)
General
- Communication interface
- WiFi, RS485, CAN
- Display
- LCD (colourful touch LCD)
- Operating temperature range
- −40 °C to +60 °C, >45 °C derating
- Permissible ambient humidity
- 0–100%
- Permissible altitude
- 2000 m
- Noise
- <45 dB
- Inverter topology
- Non-isolated (solar), isolated (battery)
- Over voltage category
- OVC II (DC), OVC III (AC)
- Weight
- 24.9 kg (all sizes)
- Cabinet size (W×H×D)
- 330 × 580 × 232 mm (excluding connectors and brackets)
- Protection degree
- IP65
- Protection level
- Class I
- Type of cooling
- Intelligent air cooling
- Warranty
- 10 years (Deye AU/NZ SUN Series warranty V2.17 covers all SUN Series AU hybrid inverters; the AU datasheet prints 10 years for every size)
- Grid regulation
- AS/NZS 4777.2
- Safety / EMC standard
- IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
Highlights
- Seven sizes, one footprint. 3.6, 5, 6, 7, 7.6, 8 and 10 kW, all 330 × 580 × 232 mm and 24.9 kg.
- AC-coupling retrofit. Add storage to an existing grid-tied solar system without replacing the original inverter.
- Up to 16 units in parallel for on-grid and off-grid operation, with multiple batteries in parallel.
- Up to 210 A battery charge/discharge (10 kW model) into a 48 V (40–60 V) lead-acid or lithium-ion bank, with self-adaption to the battery BMS.
- Dual MPPT. The 3.6–6 kW models take one string per tracker (18 A each); the 7–10 kW models take two (32 A per tracker).
- Six charge/discharge time periods, generator-energy storage, colourful touch LCD and an IP65 outdoor rating.
Model comparison
| 3.6K | 5K | 6K | 7K | 7.6K | 8K | 10K | |
|---|---|---|---|---|---|---|---|
| Rated AC power (W) | 3600 | 5000 | 6000 | 7000 | 7600 | 8000 | 9999 |
| Rated (= max.) AC current (A) | 15.7 | 21.8 | 26.1 | 30.5 | 33.1 | 34.8 | 43.5 |
| Max. continuous passthrough, grid→load (A) | 35 | 35 | 40 | 50 | 50 | 50 | 50 |
| Max. battery charge / discharge current (A) | 90 | 120 | 135 | 175 | 190 | 190 | 210 |
| Max. PV input power (W) | 5760 | 8000 | 9600 | 11200 | 12160 | 12800 | 16000 |
| Max. PV access power (W) | 7200 | 10000 | 12000 | 14000 | 15200 | 16000 | 20000 |
| MPP trackers / strings | 2 / 1+1 | 2 / 1+1 | 2 / 1+1 | 2 / 2+2 | 2 / 2+2 | 2 / 2+2 | 2 / 2+2 |
| Max. operating PV current (A) | 18+18 | 18+18 | 18+18 | 32+32 | 32+32 | 32+32 | 32+32 |
| Max. PV short-circuit current (A) | 27+27 | 27+27 | 27+27 | 48+48 | 48+48 | 48+48 | 48+48 |
| Full-load MPPT range (V, manual) | 300–425 | 300–425 | 300–425 | 200–425 | 200–425 | 200–425 | 250–425 |
| Max. output fault current (A, manual) | 36 | 50 | 60 | 70 | 76 | 80 | 100 |
| Max. output overcurrent protection (A, manual) | 80 | 80 | 80 | 140 | 140 | 140 | 140 |
| AC cable, grid / load / GEN (manual) | 6 mm² | 6 mm² | 6 mm² | 10 mm² | 10 mm² | 10 mm² | 10 mm² |
| AC breaker, grid and backup load (manual) | 40 A | 40 A | 40 A | 50 A | 50 A | 50 A | 50 A |
| Battery cable (manual) | 25 mm² | 35 mm² | 50 mm² | 70 mm² | 70 mm² | 70 mm² | 95 mm² |
| Warranty | 10 years | 10 years | 10 years | 10 years | 10 years | 10 years | 10 years |
Rows marked “manual” come from the AU user manual V1.1.0; every other row is from the July 2026 AU datasheet.
Good to know for AU installs
- The “10K” is rated 9999 W / 9999 VA, not 10 kW.
- Grid code AS/NZS 4777.2. Set the correct region and grid-protection profile at commissioning. The manual states that only DRM0 of the AS/NZS 4777 demand response modes is available.
- Earthing. The manual’s Australia/New Zealand wiring figure (section 3.11) links neutral and earth at the switchboard’s E-N link and marks the backup port’s PE wire as not required in Australia and New Zealand. Confirm the backup circuit’s earthing arrangement for the site before installing.
- RCD. The inverter has built-in leakage-current detection. The manual’s wiring figure for “grid systems without special requirements” shows a 300 mA RCD (recommended) on the inverter’s grid side; its Australia/New Zealand figure shows RCDs on the backup-load and home-load circuits, with no rating printed. The earthing section warns that any external leakage-current device protecting the inverter (Type A) must operate at 300 mA or more, or the inverter may not work properly. Deye’s figures are examples, so confirm the RCD arrangement for the site before installing.
- Protection and cables. The manual requires a separate external AC breaker between the inverter and the grid and between the inverter and the backup load (40 A for 3.6–6 kW, 50 A for 7–10 kW), and a separate DC over-current protector or disconnect between the battery and the inverter. The cable sizes in the table are Deye’s recommendation; size the final installation to AS/NZS 3000 and the site conditions.
- Export limiting. The manual draws a CT clamped on the grid-side live conductor, and two meter options: a CHINT meter and a direct-connect Eastron meter. The meter Suncloud supplies is the Eastron SDM120CTM-40mA with its ESCT-TA16 CT.
- Parallel systems: the manual says to choose the “Zero export to CT” mode (section 3.13).
- Batteries. Deye’s 48 V-class LFP modules such as RW-M6.1-B, RW-F10.2 and SE-G5.1 Pro-B have operating voltages (see their pages) inside this inverter’s 40–60 V battery window. Size the bank so its continuous current covers the inverter’s max. charge/discharge current (90–210 A, depending on size).
- Warranty. 10 years. Deye’s AU/NZ SUN Series limited warranty (V2.17, July 2026) covers all SUN Series AU hybrid inverters and names the 7, 7.6, 8 and 10 kW AM2-P models in its table; the AU datasheet prints 10 years for every size in the series.
Figures are from Deye’s AU datasheet for the SUN-(3.6-10)K-SG05LP1-AU-AM2-P (July 2026). Rows marked “manual” (full-load MPPT range, output fault current, overcurrent protection, cable and breaker sizes) and the DRM, earthing, RCD, meter and parallel notes are from the AU user manual V1.1.0 (July 2026, sections 3.4, 3.5, 3.7–3.13 and 9). The warranty terms are from Deye’s AU/NZ SUN Series 10-year limited warranty (V2.17, July 2026, p. 2). Confirm the exact model variant against the linked datasheet before quoting or commissioning.
Plan & design
Before anything is ordered — sizing, pairing and design decisions for the SG05LP1 AM2-P Single-Phase Hybrid · 3.6–10 kW.
Pairs with
Install & commission
On the wall, wired, energised and registered — in the order the job actually runs.
Operate & configure
Monitoring, tariffs, work modes — getting the most out of the system after handover.
- Guide Deye system work modes explained intermediate · 6 min read
- Guide Set up Time-of-Use (TOU) on a Deye system intermediate · 6 min read
- Guide Connect a Deye battery to Amber Electric (Deye Copilot) intermediate · 5 min read
- Guide Deye Copilot — setup, settings and AI strategies intermediate · 7 min read
- Guide Connect a logger to Wi-Fi & DeyeCloud beginner · 5 min read
- Guide 4G logger setup beginner · 3 min read
- Guide Deye warranty explained (AU / NZ) beginner · 5 min read
Troubleshoot
Known issues for this model, worst first — and every fault code it can show.
- Check W04 warning — meter address collision (001 / 002) The inverter raises a W04 warning — often right after enabling Grid Tie Meter2, even on a …
- Info Deye fault (F) code reference The inverter LCD or DeyeCloud shows an F-code (e.g. F13, F55, F58) and you need to know wh…
- Info Logger keeps going offline in DeyeCloud The plant shows offline / stale data in DeyeCloud, or the Wi-Fi logger won't connect to th…