Suncloud Energy — Deye Technical Hub
Info fault code

Deye fault (F) code reference

Symptom: The inverter LCD or DeyeCloud shows an F-code (e.g. F13, F55, F58) and you need to know what it means and where to start.

Deye SUN-series hybrid inverters report faults as F-codes on the LCD and in DeyeCloud. The table below is the complete list from the official Deye hybrid user manual (Chart 7-1 Fault information), with the first thing to check for each. Meanings vary slightly by model and firmware — confirm the exact definition in that model’s user manual before acting.

CodeMeansFirst check
F01DC input polarity reversedPV string polarity (+/−) at the inverter
F07DC start failure — BUS voltage can’t build from PV/batteryPower-cycle cleanly; if it persists, service
F13Working-mode / grid changeGrid code & battery-mode setting; usually self-clears — see F13
F15AC over-current (software)Backup + household load within the inverter rating; restart
F16AC leakage currentPV-side cable earth/ground connection; restart 2–3×
F18AC over-current (hardware)Backup + household load within rating; restart
F20DC over-current (hardware)PV & battery connections; off-grid + big load can trip it — reduce load, then power-cycle
F21BUS over-currentPV input current & battery current settings; restart 2–3×
F22Emergency stop / remote shutdownDRM or remote-off input — the inverter is being told to stop
F23Leakage (residual) current, transientPV-side cable earth/ground connection; restart 2–3×
F24DC insulation (ISO) too lowPV array + inverter connections; PE/earth cable to ground; wet MC4/DC connectors
F26DC busbar unbalancedUneven 3-phase load or DC leakage; restart 2–3×
F29Parallel CAN-bus faultParallel comms cable, address & termination (self-clears once all units are ON)
F34AC over-currentBackup load within the allowed range
F41Parallel system stopOne paralleled unit is off → all units report F41; check each unit’s status
F42AC line low voltage (grid)Grid voltage vs the AS/NZS 4777.2 window; AC cabling firm
F46Backup battery faultEach battery’s voltage / SOC / parameters match across the bank
F47AC over-frequency (grid)Grid frequency vs spec; AC cabling
F48AC under-frequency (grid)Grid frequency vs spec; AC cabling
F55DC busbar voltage too highBattery voltage too high? PV input voltage within the MPPT range?
F56DC busbar voltage too lowBattery voltage low — charge it from PV or grid
F58BMS communication faultBattery comms cable on the BMS RS485 port; battery on — see battery not charging
F62DRM0 stop (Australia only)DRM (demand-response) input — confirm it’s meant to be active; restart the system
F63ARC faultPV module cable connection; find & clear the arc-fault, then reset
F64Heat-sink over-temperatureVentilation, ambient temp & airflow; power off ~10 min then restart

Some models and firmware report a few additional or differently-worded codes (e.g. a no-grid or over-voltage variant) — always cross-check the exact code against that model’s manual.

General approach

  1. Read the exact code and description on the LCD / DeyeCloud alarm.
  2. Power-cycle cleanly (AC off → DC off → battery off, then reverse) — many faults are transient and clear on restart.
  3. If it recurs, capture a photo of the alarm and the wiring and lodge it with Suncloud support with the code, model and serial number.

This is an orientation aid, not a substitute for the manual. Don’t reset away a protection fault — F23 / F24 (leakage / insulation) point to genuine earthing or insulation issues, and F16 / F63 to a cable or arc-fault problem, that must be resolved rather than cleared.