Hybrid inverter Three-phase HV
SG01HP3 Three-Phase HV Hybrid · 10–25 kW
SUN-10/12/15/20/25K-SG01HP3-AU-AM2
10–25 kW
High-voltage three-phase hybrid, 10–25 kW. 160–700 V battery for higher efficiency, 100% unbalanced output, dual MPPT and up to 16 units in parallel — the entry HV hybrid for commercial storage paired with HV batteries such as BOS-G.
Commercial
- Rated AC power
- 10 / 12 / 15 / 20 / 25 kW
- Phase
- Three (220/380 V, 230/400 V)
- Battery
- HV Lithium-ion, 160–700 V, up to 50 A
- Max. PV input power
- 15–37.5 kW
- Unbalanced output
- 100%
- Max. efficiency
- 97.6%
- Parallel
- Up to 16 units
- Warranty
- 10 years
Specs auto-extracted from the datasheet — confirm against the linked PDF before quoting.
Specifications
Battery input
- Battery type
- Lithium-ion (self-adaption to BMS)
- Battery voltage range
- 160–700 V
- Max. charge / discharge current
- 37 A (10/12/15/20K) · 50 A (25K)
- Number of battery inputs
- 1
PV input
- Max. PV access power
- 20000 / 24000 / 30000 / 40000 / 50000 W
- Max. PV input power
- 15000 / 18000 / 22500 / 30000 / 37500 W
- Max. PV input voltage
- 1000 V
- Start-up voltage
- 180 V
- MPPT voltage range
- 150–850 V
- Rated PV input voltage
- 600 V (10–20K) · 700 V (25K)
- Max. operating PV current
- 20+20 A (10K) · 26+20 A (12/15/20K) · 26+26 A (25K)
- Max. input short-circuit current
- 30+30 A (10K) · 39+30 A (12/15/20K) · 39+39 A (25K)
- No. of MPP trackers / strings
- 2/(1+1) (10K) · 2/(2+1) (12/15/20K) · 2/(2+2) (25K)
AC output
- Rated AC input/output active power
- 10000 / 12000 / 15000 / 20000 / 25000 W
- Max. AC apparent power
- 10000 / 12000 / 15000 / 20000 / 25000 VA
- Rated AC input/output current
- 14.5 / 17.4 / 21.8 / 29 / 36.3 A
- Grid voltage / range
- 220/380 V · 230/400 V, 0.85Un–1.1Un
- Grid frequency / range
- 50 Hz (45–55 Hz) · 60 Hz (55–65 Hz)
- Grid connection
- 3L + N + PE
- Unbalanced output
- 100%
- Max. continuous passthrough (grid→load)
- 40 A (10K) · 80 A (12–25K)
- Peak power (off-grid)
- 1.5× rated, 10 s
- Power factor adjustment range
- 0.8 leading to 0.8 lagging
- THDi
- <3%
Efficiency
- Max. efficiency
- 97.6%
- Euro efficiency
- 97.0%
- MPPT efficiency
- >99%
General
- Operating temperature
- −40 to +60 °C (derating >45 °C)
- Permissible humidity
- 0–100%
- Permissible altitude
- 2000 m
- Noise
- ≤55 dB
- Surge protection
- Type II (DC), Type II (AC)
- Protection degree
- IP65
- Topology
- Non-isolated
- Cooling
- Intelligent air cooling
- Dimensions (W×H×D)
- 408 × 638 × 237 mm
- Weight
- 30.5 kg
- Communication
- WiFi, RS485, CAN
- Grid standard
- AS/NZS 4777.2
- Warranty
- 10 years
Highlights
- High-voltage battery (160–700 V) for higher round-trip efficiency — pairs with an HV battery such as BOS-G.
- 100% unbalanced output across the three phases.
- Up to 16 units in parallel for on-grid and off-grid operation, with support for multiple batteries in parallel.
- AC-coupling to retrofit an existing solar system, plus support for storing energy from a diesel generator.
- Six charge/discharge time periods for time-of-use and VPP scheduling.
Figures are from the official Deye SUN-10/12/15/20/25K-SG01HP3-AU-AM2 datasheet — confirm the exact variant against the linked datasheet before quoting or commissioning.