GE-F128 Series Outdoor C&I Battery Cabinet · 96.5–128.6 kWh
GE-F96-BC-2-A2 / GE-F112-BC-2-A2 / GE-F128-BC-2-A3
96.46–128.61 kWh
Deye ORION E air-cooled outdoor battery cabinet for C&I storage. Six, seven or eight 16.08 kWh LFP packs (314 Ah) give 96.46, 112.53 or 128.61 kWh, all of it usable under Deye's test conditions. The PDU, air conditioning and fire protection are built into one IP55, C4-M enclosure. A Deye SG01HP3 or SG02HP3 hybrid mounts on the cabinet's side wall, and each cabinet takes one GE-F128-AP accessory kit.
- System energy
- 96.46 / 112.53 / 128.61 kWh (6 / 7 / 8 packs) · 100% usable
- Models
- GE-F96-BC-2-A2 · GE-F112-BC-2-A2 · GE-F128-BC-2-A3
- Pack
- BOS-B-Pack16-A3 · 16.08 kWh · 51.2 V · 314 Ah LFP
- System voltage
- 307.2 / 358.4 / 409.6 V nominal (240–467.2 V operating)
- Rated DC power
- 48 / 56 / 64 kW
- Charge / discharge current
- 157 A recommended · 180 A max. continuous
- Inverter
- SUN-29.9–50K-SG01HP3 or SUN-60K-SG02HP3 hybrid, mounted on the cabinet (GE-F128)
- Enclosure
- IP55 · C4-M anti-corrosion (up to C5 on request) · smart air cooling · floor mount
- Cycle life
- ≥8000 (25 °C ± 2 °C, 0.5P, 70% EOL)
- Warranty
- 10 years per Deye brochure (all three sizes) — confirm terms with Suncloud
Specifications
Models
- GE-F96-BC-2-A2
- 6 packs · 96.46 kWh · 307.2 V (240–350.4 V) · 48 kW rated DC · 1460 kg
- GE-F112-BC-2-A2
- 7 packs · 112.53 kWh · 358.4 V (280–408.8 V) · 56 kW rated DC · 1575 kg
- GE-F128-BC-2-A3
- 8 packs · 128.61 kWh · 409.6 V (320–467.2 V) · 64 kW rated DC · 1690 kg
Battery pack
- Pack model
- BOS-B-Pack16-A3
- Cell type
- LiFePO4
- Pack capacity
- 314 Ah
- Pack nominal voltage
- 51.2 V
- Pack energy
- 16.08 kWh
- Pack max. charge / discharge current
- 180 A
- Pack operating temperature
- Charge 0–55 °C · Discharge −20–55 °C
System
- Packs in series
- 6 / 7 / 8
- System nominal energy
- 96.46 / 112.53 / 128.61 kWh
- System usable energy
- 96.46 / 112.53 / 128.61 kWh (100% DoD, 0.5P charge and discharge, 25 °C; may vary with system configuration)
- System nominal voltage
- 307.2 / 358.4 / 409.6 V
- System operating voltage
- 240–350.4 / 280–408.8 / 320–467.2 V
- Rated DC power
- 48 / 56 / 64 kW
- Recommended charge / discharge current
- 157 A (varies with temperature and SOC)
- Max. continuous charge / discharge current
- 180 A
- Peak discharge current
- 285 A for 15 s (20–45 °C)
- Scalability
- Up to 10 cabinets in DC parallel (1.28 MWh) · up to 10 cabinet-and-inverter units in AC parallel, on- or off-grid (0.6 MW with 60 kW inverters)
Power distribution unit
- Model
- BOS-B-PDU-2-A
- Operating voltage
- 200–1000 V DC
- Nominal charge / discharge current
- 180 A
- AC input rating
- 220 V AC ±10%, 2 A
Accessory kit (one per cabinet)
- GE-F128-AP-A
- For inverters with a single or dual battery port ≤100 A · 2 + 2 × 3AWG DC cables (3000 mm), communication cable (3000 mm), inverter mounting bracket, cable cover
- GE-F128-AP-B
- For inverters with a single battery port ≤160 A · 1AWG positive and negative DC cables (3000 mm), communication cable (3000 mm), inverter mounting bracket, cable cover
General
- Fire protection
- Aerosol fire suppression and water fire-fighting inlet · heat, smoke and CO detection · active exhaust · deflagration venting
- Cooling method
- Smart air cooling (built-in air conditioner, closed air loop)
- Communication
- CAN, RS485 (CAN 2.0, Modbus RS485)
- Operating temperature
- −30 to 55 °C (derated above 45 °C)
- Recommended storage temperature
- 0–35 °C
- Humidity
- 5–95% RH, non-condensing
- Altitude
- 3000 m
- IP rating
- IP55
- Anti-corrosion level
- C4-M standard, customisable up to C5
- Dimensions (W×D×H)
- 998 × 1240 × 2405.5 mm
- Weight
- 1460 / 1575 / 1690 kg
- Installation
- Floor mount, on a purpose-designed foundation of concrete or another non-combustible surface
- Clearance
- 100 mm between cabinets and to walls · 1500 mm at the front
- Auxiliary supply
- Three-phase L1/L2/L3/N/PE (380/400 V in the EU manual), up to 2.6 kW per cabinet · cable not supplied
- Cycle life
- ≥8000 (25 °C ± 2 °C, 0.5P, 70% EOL)
- Certification
- UN38.3, CE, IEC 62619, IEC 62477, IEC 62933-5-2, UL 9540A
- Warranty
- 10 years for GE-F96, GE-F112 and GE-F128 — Deye's AU brochure prints 10 years for the whole GE-F128 Series · confirm terms with Suncloud
Highlights
- Three capacities, one cabinet. Six, seven or eight 16.08 kWh LiFePO4 packs (314 Ah) give 96.46, 112.53 or 128.61 kWh at 307.2–409.6 V nominal. Under Deye’s test conditions (100% DoD, 0.5P, 25 °C) all of it is usable.
- The inverter mounts on the cabinet. The cabinet’s side wall has a preset bracket position for the hybrid inverter, so the inverter needs no wall mounting or drilling. Each cabinet takes one GE-F128-AP accessory kit, which holds the DC cables, communication cable, bracket and cable cover.
- Six-layer safety design. Deye lists electrical isolation, fire detection, active exhaust, explosion venting, fire suppression and thermal isolation. Inside the cabinet are heat, smoke and CO detectors and an aerosol fire-suppression unit. Outside are a water fire-fighting inlet and an emergency power-off button on the front, and a deflagration vent on the roof.
- Smart air cooling. A built-in air conditioner sends cooled air through ducts to the battery packs and power components in a closed loop. The cabinet operates from −30 to 55 °C, derated above 45 °C. It is rated IP55, with C4-M anti-corrosion as standard (C5 on request).
- Long-life LFP. Deye’s AU brochure rates the cabinet at ≥8000 cycles (25 °C ± 2 °C, 0.5P, 70% EOL).
- Scales both ways. Up to 10 cabinets run in DC parallel for capacity (1.28 MWh), or up to 10 cabinet-and-inverter units in AC parallel, on- or off-grid (0.6 MW). Cabinets can stand back to back or side by side.
Choosing the model and inverter
| Model | Packs | Energy | Nominal voltage | Rated DC power | Hybrid builds in Deye’s AU documents |
|---|---|---|---|---|---|
| GE-F96-BC-2-A2 | 6 | 96.46 kWh | 307.2 V | 48 kW | SUN-29.9K-SG01HP3 (3-hour system) |
| GE-F112-BC-2-A2 | 7 | 112.53 kWh | 358.4 V | 56 kW | SUN-50K-SG02HP3-AU-BM4-P (2-hour system), marked “coming soon” |
| GE-F128-BC-2-A3 | 8 | 128.61 kWh | 409.6 V | 64 kW | SUN-29.9–50K-SG01HP3 · SUN-60K-SG02HP3 (2-hour) · SUN-40K-SG01HP3 (3-hour) · SUN-29.9K-SG01HP3 (4-hour) |
Deye’s AU configuration list (V1.0, 2026-09-10) has one GE-F128 build: one GE-F128-BC-2-A3 cabinet and one GE-F128-AP-A kit with a SUN-29.9–50K-SG01HP3-AU-BM3/BM4 hybrid. Deye’s AU brochures (2026-09-04) add the SUN-60K-SG02HP3-AU-EM6 for a two-hour system; see the SUN-60–80K-SG02HP3 page. The 70–80 kW SG02HP3 models are not listed for this cabinet.
The GE-F96 and GE-F112 are not in the AU configuration list. Deye’s AU brochures pair the GE-F96 with the SUN-29.9K-SG01HP3-AU-BM3. They pair the GE-F112 with the SUN-50K-SG02HP3-AU-BM4-P, an inverter they mark as coming soon and which does not appear in Deye’s AU configuration list. Confirm the inverter for either model with Suncloud.
For 176.8–257.2 kWh in one cabinet, see the GE-F240/F256 Series.
Accessory kits (one per cabinet)
Each cabinet takes one of the two kits.
- GE-F128-AP-A is for inverters with a single or dual battery port up to 100 A, and it is the kit in Deye’s AU SUN-29.9–50K-SG01HP3 build. Deye’s manual (§4.2) also lists it for the 60 kW SG02HP3-EM6 (and the 30/40 kW SG02HP3). The SUN-60K-SG02HP3-AU-EM6 in the two-hour build has two 80 A battery inputs, which is within AP-A’s 100 A limit per port. It contains 2 positive and 2 negative 3AWG DC cables (3000 mm), a communication cable (3000 mm), the inverter mounting bracket and a cable cover.
- GE-F128-AP-B is for inverters with a single battery port up to 160 A. It contains 1AWG positive and negative DC cables (3000 mm), a communication cable (3000 mm), the bracket and a cable cover. Deye’s EU manual lists it for its 50 kW SG02HP3-BM4-P inverter only, and the AU version of that inverter is marked coming soon.
Site and installation notes
- The cabinet needs a three-phase auxiliary supply (L1/L2/L3/N/PE) of up to 2.6 kW per cabinet. The auxiliary cable is not supplied (manual §5.3.5).
- The manual (§6.2) makes black start available when two conditions are met: the ambient temperature is between −10 and 50 °C, and the cabinet’s auxiliary supply is fed from the LOAD port of the designated hybrid inverter. If the site needs black start, plan the auxiliary supply that way.
- Leave 100 mm between cabinets and to walls, and 1500 mm clear at the front (manual §4.1.1).
- The cabinet is floor-mounted on a purpose-designed foundation of concrete or another non-combustible surface (manual §4.1.2), and weighs up to 1690 kg.
- The manual’s siting distances are generic. Confirm the Australian siting and fire requirements for each project.
Model naming
This page follows Deye’s AU part-number list (V1.0, 2026-09-10). It names the six- and seven-pack models GE-F96-BC-2-A2 and GE-F112-BC-2-A2, and the eight-pack model GE-F128-BC-2-A3. Deye’s AU brochures and the user manual print all three with the -A3 suffix. The part-number list describes the GE-F96 and GE-F112 as reduced-pack versions of the GE-F128. Confirm the suffix when ordering.
Figures are from Deye’s ORION E GE-F128 Series Outdoor Battery Cabinet brochure (AU, V1.0, 2026-09-04), the ORION E GE-F128/F240/F256 + hybrid inverter + PCS 100–125 kW brochure (AU, V1.0, 2026-09-04), the GE-F128 Series user manual (EU edition, EN, V03, Issue A03, 2026-08) and Deye’s AU part-number and configuration list (V1.0, 2026-09-10). The manual is Deye’s EU edition, so follow Australian standards and local requirements for siting and wiring. The cycle life is the figure and test conditions printed in Deye’s AU GE-F128 Series brochure. Confirm the model suffix, accessory kit, inverter pairing and warranty terms with Suncloud before quoting or ordering.
Plan & design
Before anything is ordered — sizing, pairing and design decisions for the GE-F128 Series Outdoor C&I Battery Cabinet · 96.5–128.6 kWh.
Pairs with
Operate & configure
Monitoring, tariffs, work modes — getting the most out of the system after handover.
Documents
Everything published for the GE-F128 Series Outdoor C&I Battery Cabinet · 96.5–128.6 kWh — and where something is missing, it says so instead of hiding the row.
System & shared documents
Not specific to the GE-F128 Series Outdoor C&I Battery Cabinet · 96.5–128.6 kWh — these apply across the range and live here once, not copied per model.